Images are representations only.

OPTITEMP TT 60 C/R Universal Temperature Transmitter

Brand: Krohne
The OPTITEMP TT 60 C/R series feature extremely accurate measurements as well as sensor and process information.

With five connection terminals, new functions such as two redundant Pt100 in 3-wire connections are included.

Programming is done either using the Krohne / Inor software ProfiSoft via PC or using the Profibus network.

The OPTITEMP TT 60 series consists of 2 different versions in terms of mounting. The TT 60 R is the the rail-mount version whereas the TT 60 C is primarily intended to be mounted in a "B connection head" or larger in accordance with DIN EN 50446.

Alternatively, you can also mount the in-head version on a DIN rail according to EN 60715 with the help of an optionally available rail mounting kit.
Features
  • Up to 125 transmitters in one Profibus network
  • Profile version 3.0, A and B
  • Completely universal, linearized and separate
  • Input: resistance thermometers, thermocouples, mV and Ohms
  • Double Pt100 in 3-wire connection and TC input
  • Several outputs: input value from channel 1 and channel 2, process value to scale, redundancy with double sensor elements, arithmetic functions (difference, mean value, minimum and maximum)
  • Easy wiring, large center hole
  • Sensor error correction
  • 50-point linearization: each sensor can be adapted
  • Excellent sensor monitoring functions such as: sensor break, sensor short circuit, detection of low sensor isolation, sensor drift
  • Robust design, tested for 5g vibration
  • Integrated in the siemens PDM system
show more
The OPTITEMP TT 60 C/R series feature extremely accurate measurements as well as sensor and process information.

With five connection terminals, new functions such as two redundant Pt100 in 3-wire connections are included.

Programming is done either using the Krohne / Inor software ProfiSoft via PC or using the Profibus network.

The OPTITEMP TT 60 series consists of 2 different versions in terms of mounting. The TT 60 R is the the rail-mount version whereas the TT 60 C is primarily intended to be mounted in a "B connection head" or larger in accordance with DIN EN 50446.

Alternatively, you can also mount the in-head version on a DIN rail according to EN 60715 with the help of an optionally available rail mounting kit.
Features
  • Up to 125 transmitters in one Profibus network
  • Profile version 3.0, A and B
  • Completely universal, linearized and separate
  • Input: resistance thermometers, thermocouples, mV and Ohms
  • Double Pt100 in 3-wire connection and TC input
  • Several outputs: input value from channel 1 and channel 2, process value to scale, redundancy with double sensor elements, arithmetic functions (difference, mean value, minimum and maximum)
  • Easy wiring, large center hole
  • Sensor error correction
  • 50-point linearization: each sensor can be adapted
  • Excellent sensor monitoring functions such as: sensor break, sensor short circuit, detection of low sensor isolation, sensor drift
  • Robust design, tested for 5g vibration
  • Integrated in the siemens PDM system
1 model matching criteria
  • Product - OPTITEMP TT 60 C/R
  • Model - TT 60 C
Out of Stock

Specifications

Brand

Accuracy

  • 0.1° C (0.18° F) Typical - Pt100

Ambient Temperature Range

  • -20° to 70° C (-4° to 158° F) - TT 60 R
  • -40° to 85° C (-40° to 185° F) - TT 60 C

Applications

  • Chemical Industry
  • Food & Beverage
  • Iron, Steel & Metal Industries
  • Oil & Gas Applications
  • Pharmaceutical
  • Power Plants
  • Pulp & Paper

Approvals & Certifications

  • CE Ex II 3 G EEx NL IIC, 0102 Ex II 1 G Ex ia IIC
  • Demko 06-ATEX-141337X

Capacitance

  • 1 NF - Bus Connection (Input)
  • 10 NF - Communications Connection (Input)
  • 1000 NF - Sensor Connection (Output for TT 60 C Version)
  • 166 NF - Sensor Connection (Output for TT 60 C Ex-Version)

Communication

  • PROFIBUS PA

Consumption

  • 11 mA - Power Consumption

Electrical Connectors

  • Shielded Cable

Environmental Protection

  • IP20
  • IP54

Inductance

  • 1 µH - Communications Connection (Input)
  • 10 µH - Bus Connection (Input)
  • 750 MH - Sensor Connection (Output)

Input

  • -10 to 1,000 mV
  • 17.5 Vdc, Max.
  • 380 mA - Max.
  • 450 mA - Max.
  • 8 Vdc, Max.

Input Power

  • 5.32 W, Max.
  • 800 mW, Max.

Isolation

  • 1,500 Vac, 1 Minute - Galvanic

Mounting

  • DIN Form B Connection Head - According to DIN 43729
  • M4 Screw
  • Rail Mounting - According to EN 50020, 35 mm

Output

  • 17.5 Vdc - Sensor Connection
  • 56 mA - Sensor Connection

Output Power

  • 244 mW - Sensor Connection

Power Supply

  • 9-17.5 Vdc - TT 60 C
  • 9-32 Vdc - TT 60 R

Resistance

  • 0 to 4,000 ohms - Input Resistance

RTD Type

  • Ni100
  • Ni1000
  • Ni120
  • Ni50
  • Potentiometer
  • Pt10
  • Pt100
  • Pt1000
  • Pt200
  • Pt50
  • Pt500

Sensor, Probe Connection

  • 2-Wire
  • 3-Wire
  • 4-Wire

Sensor, Probe Type

  • B Thermocouple
  • C Thermocouple
  • D Thermocouple
  • E Thermocouple
  • G Thermocouple
  • J Thermocouple
  • K Thermocouple
  • L Thermocouple
  • N Thermocouple
  • RTD
  • R Thermocouple
  • S Thermocouple
  • T Thermocouple
  • U Thermocouple

Temperature Range

  • -200° to 250° C (-328° to 482° F) - Ni50, Ni100, Ni120, Ni1000
  • -200° to 850° C (-328° to 1,562° F) - Pt10, Pt50, Pt100, Pt200, Pt500, Pt1000