microLoad.net™ Preset

Brand: TechnipFMC
The Smith Meter® microLoad.net is a microprocessor-based instrument with Ethernet capability.

It is designed to monitor and control a single-product straight loading and unloading.

The unit can operate either as a stand-alone instrument or be part of system in which it communicates with an automation or supervisory control and data acquisition (SCADA) system.
Features
  • One arm, single-product loading and unloading
  • Standalone or remote controlled operation
  • Lease automation custody transfer (LACT) control with basic sediment and water (BS&W) monitoring, sampling, and diverting
  • Ethernet communications port
  • Modbus and Smith communication protocols
  • Event, transaction, and weights and measures audit logging
  • User configurable load ticket and display
  • Automatic volume correction of refined and crude liquids from liquified petroleum gas (LPG) to asphalt based on temperature, pressure, and density using API MPMS CH.11.1-2004 tables and all industry standard calculations
  • Promass Coriolis meter communications for density and status
  • Globally weight and measures and electrical safety approved
  • Built in web server for browser access
  • Transaction log export to spreadsheet
  • Programmable pulse output
  • Fully programmable flow profile
  • Display backed-up per International Organization of Legal Metrology (OIML)
  • Three levels of parameter access security
  • Automated proving assistance
  • Boolean and algebraic custom logic expressions
  • Additization of metered or unmetered products
  • microMate configuration utility included
  • Continuous monitoring of critical functions
  • Configurable language and messages
  • Pulse security level B
show more
The Smith Meter® microLoad.net is a microprocessor-based instrument with Ethernet capability.

It is designed to monitor and control a single-product straight loading and unloading.

The unit can operate either as a stand-alone instrument or be part of system in which it communicates with an automation or supervisory control and data acquisition (SCADA) system.
Features
  • One arm, single-product loading and unloading
  • Standalone or remote controlled operation
  • Lease automation custody transfer (LACT) control with basic sediment and water (BS&W) monitoring, sampling, and diverting
  • Ethernet communications port
  • Modbus and Smith communication protocols
  • Event, transaction, and weights and measures audit logging
  • User configurable load ticket and display
  • Automatic volume correction of refined and crude liquids from liquified petroleum gas (LPG) to asphalt based on temperature, pressure, and density using API MPMS CH.11.1-2004 tables and all industry standard calculations
  • Promass Coriolis meter communications for density and status
  • Globally weight and measures and electrical safety approved
  • Built in web server for browser access
  • Transaction log export to spreadsheet
  • Programmable pulse output
  • Fully programmable flow profile
  • Display backed-up per International Organization of Legal Metrology (OIML)
  • Three levels of parameter access security
  • Automated proving assistance
  • Boolean and algebraic custom logic expressions
  • Additization of metered or unmetered products
  • microMate configuration utility included
  • Continuous monitoring of critical functions
  • Configurable language and messages
  • Pulse security level B

Specifications

Brand

AC Instrument Input Power

  • Dual Voltage Input: 115 or 230 volts Alternating Current Power (VAC) via Switch Selection, 50/60 Hertz (Hz)
  • Power Consumption: Approximately 9 W
  • Power Interruption Tolerance: Interruption of Power greater than 0.05 seconds (typical) will cause an orderly Shutdown of the microFlow.net and the control valve will be immediately signaled to close

Digital (Meter Signal) Pulse Inputs

  • Type: Optically-Isolated, Solid-State Voltage Sensors
  • Quantity: Two
  • Input Voltage Range: 5 to 28 Volts Direct Current (VDC) Compatible
  • Pickup Voltage: 5 Vdc minimum
  • Drop-Out Voltage: 1 Vdc maximum
  • Current at Max. Voltage: 20 mA maximum
  • Minimum Pulse Input Frequency: 3 Hz
  • Input Level Duration: 83 microseconds (μS) minimum

Digital Control Inputs

  • Type: Optically-Isolated, Solid-State Voltage Sensors
  • Quantity: Three
  • Input Voltage Range: 5 to 28 Vdc Compatible
  • Pickup Voltage: 5 Vdc minimum
  • Drop-Out Voltage: 1 Vdc maximum
  • Current at Max. Voltage: 20 mA maximum
  • Input Level Duration: 120 milliseconds (mS) minimum

Analog Inputs

  • Type: 20-bit Analog-to-Digital Converters
  • Function: One Resistance Temperature Device (RTD), One 4-20 mA

Temperature Resistance Temperature Detector (RTD)

  • Type: Four-wire, 100-ohms Platinum RTD with a Temperature Coefficient at 32° F to be 0.00214 ohms per ohms°F (0.00385 ohms per ohms/°C)
  • Temperature Range: -148° F to +572° F (-100° C to +300° C)
  • Temperature Measurement Accuracy: ± 0.72° F (± 0.4° C) over the Specified Range

Current (4-20 mA) Input

  • Type: Two-wire, 4-20 mA Current Loop Receiver, Programmable as to Function
  • Span Adjustment: Program Adjustable
  • Input Burden: 50 ohms
  • Accuracy: ± 0.025 % of Range
  • Resolution: One part in 1,048,576
  • Voltage Drop: Two Volts maximum
  • Sampling Rate: One Sample per 300 millesecond (ms) minimum

DC Power

  • 12 Vdc ± 5 %, 180 mA maximum, Short-Circuit Protected

AC Digital Outputs

  • Type: Optically Isolated, Solid-State Output, User-Programmable as to Function
  • Quantity: Four
  • Load Voltage Range: 90 to 280 Vac Root Mean Square (RMS) 48 to 63 Hz
  • Steady-State Load Current Range: 0.05 amp (RMS) minimum to 0.50 amp (RMS) maximum into an Inductive Load
  • Leakage Current at maximum Voltage Rating: 2.5 mA maximum at 240 Vac
  • On-State Voltage Drop: 2.0 Vac at maximum Load

DC Digital Outputs

  • Type: Optically Isolated, Solid-State Open-Collector Output, User-Programmable as to Function
  • Quantity: Two
  • Switch Blocking Voltage: 30 Vdc maximum
  • Load Current: 150 mA maximum with 0.6 volt drop; Power Down - Normally Open

Pulse Output

  • Type: Optically Isolated, Solid-State Open-Collector Output; Pulse-Output Units are Program-Selectable through the microLoad.net keypad or communications
  • Switch-Blocking Voltage (Switch Off): 30 Vdc maximum
  • Load Current (Switch On): 10 mA with 0.6 Volts drop
  • Frequency Range: 0 to 3,000 Hz
  • Duty Cycle: 50/50 (On/Off)

Environmental

  • Ambient Operating Temperature: -13° F to 140° F (-25° C to +60° C)
  • Humidity: 5 to 95 % with Condensation
  • Enclosure: Explosion-proof (NEMA7, Class I, Groups C and D) and Watertight (NEMA 4X), IP65