Description
The Protego hydraulic flame arresters of type TTS/P, TS/E and TS/W are mainly designed to protect process plants which are connected to waste thermal combustion units.
Hydraulic flame arresters of the TS/P, TS/E and TS/W series are particularly suitable to protect plants which supply heavily contaminated, sticking, polymerizing or even foaming substances into thermal combustion units.
Generally it is necessary to protect the plant against in-line deflagration, stable detonation and endurance burning hazards taking into account the plant’s operating conditions.
Inventory
Displaying price & availability for Virginia, United States in USD Change Location
6 models matching criteria
- Explosion Group - Group IIA (NEC Group D)
- Length - 1,000 mm / 40"
Out of Stock
- Explosion Group - Group IIA (NEC Group D)
- Length - 2,000 mm / 80"
Out of Stock
- Explosion Group - Group IIB3 (NFPA Group C)
- Length - 2,000 mm / 80"
Out of Stock
- Explosion Group - Group IIB3 (NFPA Group C)
- Length - 1,000 mm / 40"
Out of Stock
- Explosion Group - Group IIC (NFPA Group B)
- Length - 1,000 mm / 40"
Out of Stock
- Explosion Group - Group IIC (NFPA Group B)
- Length - 2,000 mm / 80"
Out of Stock
Configure
Specifications
Specifications
Brand
Approvals & Certifications
- ATEX
- EN ISO 16852
- Group IIA NEC Group D
- NFPA Groups C & B
Approvals & Certifications
- NFPA: Group IIB3 (NFPA Group C) - TS/E, Group IIC (NFPA Group B) - TS/W
Environmental Protection
- Explosion-proof
Materials of Construction
- Sparge Pipe, Tank: Stainless Steel
- Sparge Pipe: Hastelloy
- Sparge Pipe: Plastic
- Tank: Coated Steel
- Tank: Resin
- Tank: Steel Lined with ECTFE
Operating Pressure
- psi: 0 to 15.9 (kPa: 0 to 110, bar: 0 to 1.1)
Operating Temperature
- 0° to 60° C (32° to 140° F)
Pressure Type
- Absolute
Temperature Range
- Limitation: 80° C (176° F) at the Gas Outlet