Images are representations only.

OPTITEMP TT 31 R Universal Temperature Transmitter

Brand: Krohne
Transmitters in the OPTITEMP TT 31 R series are universal, separate 1 and 2 channel two-wire transmitters, available for both ex and non-ex applications.

For hazardous (Ex) applications, no zener barriers or intrinsically safe power supply units are necessary, considerably reducing the costs for purchase and servicing.

The TT 31 R is designed to be mounted on DIN rails.
Features
  • Extremely cost-efficient solution for hazardous (Ex) applications
  • Completely universal, linearized and isolated
  • Input: resistance thermometers, thermocouples, mV and ohms
  • Sensor and system error correction (sensor/transmitter) for maximum accuracy
  • Complete access to all functions during operation
  • Constant sensor break function
  • Simple loop checking with calibrated output
  • User-friendly Windows configuration software
  • Only 11 mm per channel (2-channel version)
  • Permanent or removable connections
show more
Transmitters in the OPTITEMP TT 31 R series are universal, separate 1 and 2 channel two-wire transmitters, available for both ex and non-ex applications.

For hazardous (Ex) applications, no zener barriers or intrinsically safe power supply units are necessary, considerably reducing the costs for purchase and servicing.

The TT 31 R is designed to be mounted on DIN rails.
Features
  • Extremely cost-efficient solution for hazardous (Ex) applications
  • Completely universal, linearized and isolated
  • Input: resistance thermometers, thermocouples, mV and ohms
  • Sensor and system error correction (sensor/transmitter) for maximum accuracy
  • Complete access to all functions during operation
  • Constant sensor break function
  • Simple loop checking with calibrated output
  • User-friendly Windows configuration software
  • Only 11 mm per channel (2-channel version)
  • Permanent or removable connections

Specifications

Brand

Accuracy

  • Typical: ± 0.1 % of Measuring Span

Ambient Temperature Range

  • -20° to 70° C (-4° to 158° F)

Applications

  • Chemical Industry
  • Food & Beverage
  • Iron, Steel & Metal Industries
  • Oil & Gas Applications
  • Pharmaceutical
  • Power Industry
  • Pulp & Paper

Approvals & Certifications

  • CE 0102 II (1) G [Ex ia] IIC, 0102 II (1) D [Ex iaD]
  • Demko 06-ATEX-141334X

Communication

  • USB

Configuration

  • PC Tempsoft Software with Cable

Electrical Connectors

  • Plug Connection
  • Terminal Connection

Input

  • -10 to 500 mV

Input Signal

  • ≤ 13 mA
  • ≤ 15 Vdc
  • 100 MH
  • 550 NF

Isolation

  • Galvanic: 1,500 Vac, 1 Minute

Mounting

  • Rail Mounting According to EN 50022

Output

  • 4-20 mA, 20-4 mA Temperature Linear

Output Load

  • 0 to 1,200 ohms at 8-36 Vdc

Power Supply

  • 8-36 Vdc

Resistance

  • Potentiometer: 0 to 2,000 ohms

RTD Type

  • Ni100
  • Ni1000
  • Potentiometer
  • Pt100
  • Pt1000

Sensor, Probe Connection

  • 2-Wire
  • 3-Wire
  • 4-Wire

Sensor, Probe Type

  • AE Thermocouple
  • B Thermocouple
  • E Thermocouple
  • J Thermocouple
  • K Thermocouple
  • L Thermocouple
  • N Thermocouple
  • RTD
  • R Thermocouple
  • S Thermocouple
  • T Thermocouple
  • U Thermocouple

Temperature Range

  • Ni100, Ni1000: -60° to 250° C (-76° to 482° F)
  • Pt100, Pt1000: -200° to 1,000° C (-328° to 1,832° F)