Images are representations only.

OPTITEMP TT 11 C/R Analog Temperature Transmitter

Brand: Krohne
The OPTITEMP TT is an Analog, multirange 3-wire temperature transmitter which works together with single resistance thermometers of the type Pt100 and Pt1000.

A special feature of the device is its 0-10 Vdc output that predestines it for the HVac systems in building services applications. The transmitter has a high reliability and a good industrial performance.

The OPTITEMP TT series consists of 2 different versions in terms of the mounting. The TT 11 R is the rail-mount version for DIN rails whereas the TT 11 C is primarily intended to be mounted in a "B connection head" or larger according to DIN 43729.

As an alternative you can also mount the in-head version on a DIN rail according to DIN 50022 / EN 60715 with the help of an optionally available rail mounting kit.
Features
  • 0-10 Vdc output for building services applications
  • Rangeable with solder pads and potentiometers
  • Temperature linear output for Pt100 and Pt1000
  • Sensor break monitoring
  • Polarity protected power supply
  • Easy wiring, in-head version with large center hole
  • In-head version with moulded electronics for high protection
show more
The OPTITEMP TT is an Analog, multirange 3-wire temperature transmitter which works together with single resistance thermometers of the type Pt100 and Pt1000.

A special feature of the device is its 0-10 Vdc output that predestines it for the HVac systems in building services applications. The transmitter has a high reliability and a good industrial performance.

The OPTITEMP TT series consists of 2 different versions in terms of the mounting. The TT 11 R is the rail-mount version for DIN rails whereas the TT 11 C is primarily intended to be mounted in a "B connection head" or larger according to DIN 43729.

As an alternative you can also mount the in-head version on a DIN rail according to DIN 50022 / EN 60715 with the help of an optionally available rail mounting kit.
Features
  • 0-10 Vdc output for building services applications
  • Rangeable with solder pads and potentiometers
  • Temperature linear output for Pt100 and Pt1000
  • Sensor break monitoring
  • Polarity protected power supply
  • Easy wiring, in-head version with large center hole
  • In-head version with moulded electronics for high protection

Specifications

Brand

Accuracy

  • Typical: ± 0.15 % of Temperature Span

Adjustment

  • Fine Adjustment: ± 10 %

Alarm

  • Sensor Break Monitoring: > 11 Vdc (User-Definable Output)
  • Sensor Break Monitoring: ≤ 0 V (User-Definable Output)

Applications

  • Heating, Ventilation & Air Conditioning (HVac) in Building Services Applications
  • Temperature Measurements Especially in Building Services Applications

Approvals & Certifications

  • Calibration
  • IEC 60751

Approvals & Certifications

  • CE
  • EMC Directive: 2004/108/EC, EN 61326-1: 2006
  • NAMUR NE 21 (For Frequency ≥ 150 kHz)
  • UL

Consumption

  • Current Consumption: 12 mA

Electrical Connectors

  • Single/Stranded Wires: Max.

Electrical Protection

  • Polarity

Enclosure, Body Material

  • In-Head, Rail-Mount Transmitter: Polycarbonate

Environmental Protection

  • In-Head (with Cover), Rail-Mount Transmitter: IP20
  • In-Head Transmitter: IP10 (without Cover)

Humidity

  • 5 to 95 % Relative Humidity, Non-Condensing

Mounting

  • Clamp
  • In-Head Transmitter: B Connection Head or Larger According to DIN 43729
  • M4 Screw
  • Rail-Mount Transmitter (35 mm / 1.38”), In-Head Transmitter: Rail According to DIN 50022 / EN 60715
  • Spring

Operating Temperature

  • In-Head Transmitter: -40° to 85° C (-40° to 185° F)
  • Rail-Mount Transmitter: -20° to 70° C (-4° to 158° F)

Output

  • 0-10 Vdc, Temperature Linear for In-Head Transmitter
  • 4-20 mA- Rail-Mount Transmitter

Output Load

  • Permissible Load: Min. 10 kiloohms

Power Supply

  • In-Head, Rail-Mount Transmitter: 15-30 Vdc

Resistance

  • Maximum

RTD Type

  • Pt100
  • Pt1000

Sensor, Probe Connection

  • 3-Wire
  • 4-Wire

Sensor, Probe Material

  • Temperature-Sensitive Sensor: Platinum RTD

Sensor, Probe Type

  • RTD

Storage Temperature

  • In-Head Transmitter: -40° to 85° C (-40° to 185° F)
  • Rail-Mount Transmitter: -20° to 70° C (-4° to 158° F)

Temperature Coefficient

  • Pt100: 3.85 x 10⁻³ K⁻¹

Temperature Range

  • Zero Point: -50° to 50° C (-60° to 120° F)

Update Time

  • ≤ 200 milliseconds