Images are representations only.

FA-G In-Line Deflagration Flame Arrester

Brand: PROTEGO
The compact design of the Protego FA-G in-line deflagration flame arrester makes it the state of the art technology for installation in pipes with diameters of up to 2".

The devices are installed with minimal distance to the burner to prevent flashback in to the fuel feed lines.

When installing the deflagration flame arrester, make sure that the distance between potential ignition sources and the location of the installed device, does not exceed the L/D ratio (Pipe length/pipe diameter), for which the device was approved.

As per EN ISO 16852 the L/D ratio is limited to (L/D) maximum ≤50 for deflagration flame arresters of explosion groups IIA and IIB3 (NEC groups D and C (MESG ≥0.65 mm)) and to (L/D) maximum ≤30 for explosion group IIC (NEC group B).
Features
  • Different application possibilities
  • Modular design
  • The individual FLAMEFILTER can be quickly removed and installed
  • Threaded connection for direct mounting into pipeline
  • Bidirectional flame transmission proof design
  • Protects against deflagrations for all explosion groups
  • Use of temperature sensors for G 1-1/2" and G 2" is possible
show more
The compact design of the Protego FA-G in-line deflagration flame arrester makes it the state of the art technology for installation in pipes with diameters of up to 2".

The devices are installed with minimal distance to the burner to prevent flashback in to the fuel feed lines.

When installing the deflagration flame arrester, make sure that the distance between potential ignition sources and the location of the installed device, does not exceed the L/D ratio (Pipe length/pipe diameter), for which the device was approved.

As per EN ISO 16852 the L/D ratio is limited to (L/D) maximum ≤50 for deflagration flame arresters of explosion groups IIA and IIB3 (NEC groups D and C (MESG ≥0.65 mm)) and to (L/D) maximum ≤30 for explosion group IIC (NEC group B).
Features
  • Different application possibilities
  • Modular design
  • The individual FLAMEFILTER can be quickly removed and installed
  • Threaded connection for direct mounting into pipeline
  • Bidirectional flame transmission proof design
  • Protects against deflagrations for all explosion groups
  • Use of temperature sensors for G 1-1/2" and G 2" is possible
3 models matching criteria
  • Model - In-Line Deflagration Flame Arrester with Integrated Temperature Sensor (Size 1-1/2" to 2")
Out of Stock
  • Model - In-Line Deflagration Flame Arrester (Size 1/2" to 2")
Out of Stock
  • Model - In-Line Deflagration Flame Arrester with Two Integrated Temperature Sensors (Size 1-1/2" to 2")
Out of Stock

Specifications

Brand

Approvals & Certifications

  • ATEX
  • CEN
  • IEC
  • NEC Groups D, C (MESG ≥ 0.65 mm) & B

Approvals & Certifications

  • ISO 16852, 6358 & 16016
  • TÜV (Technischer Uberwachungsverein)

BSP Connection

  • G 1” Female
  • G 1/2” Female
  • G 1-1/2” Female
  • G 1-1/4” Female
  • G 2” Female
  • G 3/4” Female

Enclosure, Body Material

  • Hastelloy
  • Stainless Steel

Gasket Material

  • PTFE

Materials of Construction

  • Flamefilter: Copper
  • Flamefilter: Hastelloy
  • Flamefilter: Inconel
  • Flamefilter: Stainless Steel
  • Flamefilter: Tantalum

Operating Pressure

  • psi: 15.9 to 21.7 (kPa: 110 to 150, bar: 1.1 to 1.5)

Operating Temperature

  • 0° to 60° C (32° to 140° F)

Pipe Connection

  • 1” Pipe
  • 1/2” Pipe
  • 1-1/2” Pipe
  • 1-1/4” Pipe
  • 2” Pipe
  • 3/4” Pipe

Pressure Type

  • Absolute