Images are representations only.

Model TD2

Brand: Magnetrol
Thermatel® TD2 switch can easily be adjusted to detect flow (gases and liquids), level or liquid-liquid interface.

The TD2 is either Vdc or Vac line powered, has integral or remote electronics and offers additionally LED indication, time delay and mA output for diagnostics and trending.

With continuous diagnostics, automatic temperature compensation, narrow hysteresis and fast response time, the TD2 brings you the latest in thermal dispersion technology.
Features
  • Easy field calibration – pre-calibration from factory at request.
  • Variable flow or Flow/No flow detection of gases and liquids.
  • Excellent low flow sensitivity.
  • Automatic temperature compensation for repeatable alarm under varying process temperatures.
  • Continuous diagnostics detect sensor fault.
  • Continuous monitoring of flow rate versus setpoint via LED (TD2).
  • mA output provides repeatable indication of flow rate and fault detection (TD2).
  • Flow can be measured over test points (TD2).
  • Optional retractable fitting for dismantling under process conditions.
  • Process conditions up to +450 °C (+850 °F) and 414 bar (6000 psi).
  • Integral or remote electronics up to 150 m (500 ft).
  • Unique spherical tip design option ideal for liquids or high viscosity applications.
  • Suited for SIL1 and SIL2 loops (full FMEDA report available).
show more
Thermatel® TD2 switch can easily be adjusted to detect flow (gases and liquids), level or liquid-liquid interface.

The TD2 is either Vdc or Vac line powered, has integral or remote electronics and offers additionally LED indication, time delay and mA output for diagnostics and trending.

With continuous diagnostics, automatic temperature compensation, narrow hysteresis and fast response time, the TD2 brings you the latest in thermal dispersion technology.
Features
  • Easy field calibration – pre-calibration from factory at request.
  • Variable flow or Flow/No flow detection of gases and liquids.
  • Excellent low flow sensitivity.
  • Automatic temperature compensation for repeatable alarm under varying process temperatures.
  • Continuous diagnostics detect sensor fault.
  • Continuous monitoring of flow rate versus setpoint via LED (TD2).
  • mA output provides repeatable indication of flow rate and fault detection (TD2).
  • Flow can be measured over test points (TD2).
  • Optional retractable fitting for dismantling under process conditions.
  • Process conditions up to +450 °C (+850 °F) and 414 bar (6000 psi).
  • Integral or remote electronics up to 150 m (500 ft).
  • Unique spherical tip design option ideal for liquids or high viscosity applications.
  • Suited for SIL1 and SIL2 loops (full FMEDA report available).

Specifications

Brand

Approvals & Certifications

  • ATEX - II 2 G Ex d IIC T6 to T2 -40° to 60° C Gb
  • CCOE
  • CE
  • CSA
  • FM - Flameproof. Class I, Div. 1, Groups B, C, D, Temperature Codes: T2D (Ta=75° C), T3 (Ta=65° C), Class I, Zone 1, AEx d IIB + H₂, Typical 4/IP55
  • IEC
  • INMETRO
  • RosTech, FSTS

Conduit Connection

  • 1/2” NPT
  • 3/4” NPT
  • M20

Cover - for Local Enclosure

  • Blind Cover - Flameproof
  • Glass Lens Cover - Flameproof

Electronics - Standard Features

  • Adjustable Time Delay 0 to 100 seconds (Time Delay in Addition to Sensor Response)
  • Continuous Diagnostics Detect Sensor Fault
  • Detects Min. Flow or Presence / Absence of Flow
  • Easy / Fast Calibration
  • Excellent Low Flow Sensitivity
  • Hygienic Design Available
  • Non-Linear mA Output Signal Can be used for Trending, Diagnostics & Repeatable Flow/level Indication
  • Temperature Compensation

Enclosure, Body Material

  • 304 Stainless Steel
  • 316 Stainless Steel
  • Cast Aluminum A356 Containing less than 0.2 % Copper

Flange Material

  • 316 Stainless Steel
  • 316L Stainless Steel
  • Hastelloy C
  • Monel

Input Power

  • 100-264 Vac
  • 19.2-28.8 Vdc 50/60 Hz
  • 4 W at 24 Vdc
  • 5 W at 100-264 Vac
  • Power Consumption: 4.5 W at 30 Vdc

Insertion 'U' Length

  • Custom 'U' Lengths: 2” to 130” (5 cm to 330 cm) in 1” (2.5 cm) Increments

Operating Pressure - Sensor

  • Maximum

Operating Temperature - Electronics

  • -40° to 70° C (-40° to 158° F)

Operating Temperature - Sensor

  • -73° to 454° C (-100° to 850° F)
  • Extended Range: -73° to 454° C (-100° to 850° F)

Options

  • LED Indication of Flow/Level
  • Remote

Principle of Operation

  • Thermal, Calorimetric

Remote Electronics Enclosure & Cover

  • Blind Cover - Flameproof
  • Glass Lens Cover - Flameproof

Response Time

  • 1 to 10 seconds (Typical - Dependant Upon Sensor Type, Application, & Set Point Adjustment)

Sensor, Probe Style

  • Insertion

Switch Point Range

  • Air: 0.1 to 500 FPS (0.03 to 150 mps)
  • Water: 0.01 to 5.0 FPS (0.003 to 1.5 mps)

Switch Type

  • DPDT Switch: 8 Amp at 120 Vac, 250 Vac / 8 Amp at 30 Vdc, 0.5 Amp at 125 Vdc / Hermetically Sealed 1 Amp at 28 Vdc, 0.5 Amp at 125 Vdc

Wetted Materials

  • 316, 316L Stainless Steel
  • Hastelloy C
  • Monel